■ Specification【Rated current corresponding to Resistive load】
Type 型式 | Standard type / 標(biāo)準(zhǔn)型 | |||||||
Model 型號(hào) | SCR – 10LA | SCR – 25LA | SCR – 40LA | SCR – 50LA | SCR – 75LA | |||
Rated current 額定電流 | 10A max. | 25A max. | 40A max | 50A max. | 75A max | |||
I2t for fuse 熔斷電流 | 144A2S | 259A2S | 664A2S | 518A2S | 1328A2S | |||
Surge current 耐突波電流 | 135A | 275A | 410A | 550A | 820A | |||
Peak voltage 耐突波電壓 | 1200VAC min. | |||||||
Output voltage 輸出電壓 | 90 ~ 250VAC | |||||||
Type 型式 | High voltage type / 高壓型 | |||||||
Model 型號(hào) | SCR – 10LA-H | SCR – 25LA-H | SCR – 40LA-H | SCR – 50LA-H | SCR – 75LA-H | |||
Rated current 額定電流 | 10A max. | 25A max. | 40A max | 50A max. | 75A max | |||
I2t for fuse 熔斷電流 | 144A2S | 259A2S | 664A2S | 518A2S | 1328A2S | |||
Surge current 耐突波電流 | 135A | 275A | 410A | 550A | 820A | |||
Peak voltage 耐突波電壓 | 1200VAC min. | |||||||
Output voltage 輸出電壓 | 250 ~ 480VAC |
■General specification / 共同規(guī)格
輸入方式 | 4 ~ 20 mA | ||||
輸入阻抗 | Approx. 1.2KΩ | ||||
控制方式 | Phase control | ||||
洩漏電流 | 0.5% of full load max. | ||||
反應(yīng)時(shí)間 | 1.0ms max. | ||||
輸入耐突波 | 4 KVrms(EN60950/VDE0805) | ||||
電介強(qiáng)度 | 100MΩ / 500VDC(EN60950/VDE0805) | ||||
絕緣強(qiáng)度 | 100MΩ / 500VDC(EN60950/VDE0805) | ||||
外殼材質(zhì) | 防火ABS(UL: 94V0) | ||||
工作環(huán)境 | -40℃ ~ +80℃;35 ~ 85%RH |
■ Notice of safety / 安全注意事項(xiàng)
Warning
Potentially hazardous situation, if mishandling, may result in death or serious injury.
潛在危險(xiǎn),如果操作失當(dāng)可能導(dǎo)致死亡或嚴(yán)重傷害。
1> Please do not touch any terminal of this module while power supply is supplied, if do, it may result in electronic shock.
送電中,請(qǐng)勿碰觸本固態(tài)模組任何接線端子以避免觸電。
2> 「Power supply system」must to be shutdown before renew the fuse, if not, it may result in electronic shock.
更換保險(xiǎn)絲前,請(qǐng)務(wù)必關(guān)閉電源系統(tǒng)以避免觸電。
3> Please rated the load current within the specified value, if not, it may result to burn up this module or fuse.
負(fù)載電流請(qǐng)勿超過額定電流,以避免保險(xiǎn)絲或本固態(tài)模組燒毀。
4> Please tighten the screw terminal over 100kg-cm, if not, it may result to burn up this module or fuse.
請(qǐng)務(wù)必鎖緊端子螺絲,扭力須超過100kg-cm,否則可能導(dǎo)致本固態(tài)模組或保險(xiǎn)絲燒毀。
5> If this module is burned up, it may be in short circuit condition or malfunction, Please settle an independent alarm
system to ensure safety protection, if not, it may result in a serious accident.
本固態(tài)模組燒毀後可能是短路或失控狀態(tài),請(qǐng)加裝獨(dú)立警報(bào)系統(tǒng)以確保安全, 否則可能造成嚴(yán)重意外事故。
■ Notice of use / 使用注意事項(xiàng)
1> To protect the solid state module against a short-circuit of the load, please use a fuse with a I2t value < 1/2 I2t
value specified.
請(qǐng)加裝快速保險(xiǎn)絲(I2t value 小於額定值的一半),以防止因負(fù)載短路而造成固態(tài)模組燒毀。
2> The thermal conductive silicone rubber or thermal grease is required
When the solid state module is mounted on a heat sink
本固態(tài)模組加裝散熱器時(shí)務(wù)必墊高導(dǎo)熱系數(shù)的矽膠片或散熱膏【導(dǎo)熱系數(shù)(K)>4.5】。
3> The rated current is corresponding to a resistive load, if the solid state module is applied in other loads,
Please consider the inrush current at turn on and the surge voltage at turn off.
本固態(tài)模組所標(biāo)示的額定電流是以電阻性負(fù)載為準(zhǔn),如果使用在其他負(fù)載上須考慮起動(dòng)電流及關(guān)機(jī)突波。
* Electric discharge lamps: Those loads have the「inrush current」at turn on and the「surge voltage」at turn off,
please use「high voltage type」on 220VAC mains.
電子起動(dòng)式燈具(如日光燈):須考慮起動(dòng)電流及關(guān)機(jī)突波,220VAC電源系統(tǒng)請(qǐng)選用「高壓型」。
* Incandescent lamp: The rated current of the module must be over 4 times of the incandescent lamp current.
炙熱燈泡(如IR燈管): 須考慮起動(dòng)電流,固態(tài)模組的額定電流須大於炙熱燈泡電流的「四倍」。
* Three phase motors: The rated current of the s module must be over 4 times of the three phase motor average
current .
三相馬達(dá):須考慮起動(dòng)電流,固態(tài)模組的額定電流須大於三相馬達(dá)平均電流的「四倍」。
* Transformer loads: The rated current of the module must be over 10 times of the transformer current.
變壓器負(fù)載:須考慮反電動(dòng)電流,固態(tài)模組的額定電流須大於變壓負(fù)載電流的「十倍」。
* Capacitor loads, the rated current of the module must be over 3 times of the capacitor current .
電容性負(fù)載:須考慮充電瞬間電流,固態(tài)模組的額定電流須大於電容性負(fù)載電流的「三倍」。